3.
Set "Link Direct Device Setting" in "CPU Parameter" to "Extended Mode (iQ-R Series Mode)".
[CPU Parameter]  [Memory/Device Setting]  [Link Direct Device Setting]  [Link Direct Device Setting]
To write module parameters of the RJ71GN11-T2 on a CPU module using an engineering tool, set "Link Direct
Device Setting" to "Extended Mode (iQ-R Series Mode)".
If "Link Direct Device Setting" is "Q Series Compatible Mode", "Write to PLC" cannot be executed.
4.
Set the RJ71GN11-T2 as follows.
[Navigation window]  [Parameter]  [Module Information]  Right-click  [Add New Module]
5.
Click the [OK] button to add a module label of the RJ71GN11-T2.
3.2 Communication Example with CC-Link IE TSN Class A Remote Station
3 PROGRAMMING
135
3