No.
Name
SB007D
Hold/clear status
setting for CPU STOP
SB007E
Type of IP Address
SB007F
IP address setting
status
SB0086
Remote device forced
output request accept
SB0087
Remote device forced
output status
SB00B0
Data link error status of
each station
SB00B1
Data link error status of
master station
SB00C0
Reserved station
setting status
SB00D0
Error invalid station
setting current status
SB00E8
Station type match
status of each station
Description
Stores the setting status of "Output Hold/Clear Setting during CPU STOP"
under "I/O Maintenance Settings" in "Supplementary Cyclic Settings" of
"Application Settings" for the own station.
Off: Hold
On: Clear
Stores the type of IP address.
Off: IPv4
On: IPv6
Stores the status of the IP address setting by parameter.
Off: No setting
On: Set
For local stations, this relay stores the acceptance status of the IP address
from the master station.
Stores the acceptance status of the remote device test function.
Off: Not accepted
On: Accepted
Stores the operating status of the remote device test function.
Off: Not completed
On: Completed
Stores the data link status of each station.
Off: All stations normal
On: Faulty station exists
When this relay is turned on, the status of each station can be checked with
'Data link status of each station' (SW00B0 to SW00B7).
Depending on the link refresh timing, the update of 'Data link status of each
station' (SW00B0 to SW00B7) may be offset by one sequence scan.
Since a local station cannot obtain the station information of the CC-Link IE
TSN Class A remote station when communicating in multicast mode, "0: Data
link normally operating station" is reflected to the CC-Link IE TSN Class A
remote station.
(Conditions)
Reserved stations and stations that surpass the maximum station number are
ignored.
Stores the data link status of the master station.
Off: Normal
On: Error
Stores whether a reserved station is set.
Off: No setting
On: Set
When this relay is turned on, the status of each station can be checked with
'Reserved station setting status' (SW00C0 to SW00C7).
Depending on the link refresh timing, the update of 'Reserved station setting
status' (SW00C0 to SW00C7) may be offset by one sequence scan.
Set whether an error invalid station is set.
Off: No setting
On: Set
When this relay is turned on, the status of each station can be checked with
'Error invalid station setting status' (SW00D0 to SW00D7).
Depending on the link refresh timing, the update of 'Error invalid station
setting status' (SW00D0 to SW00D7) may be offset by one sequence scan.
Stores the station type match status of each station.
Off: Station type match in all stations
On: Station type mismatch exists
When this relay is turned on, the status of each station can be checked with
'Station type match status' (SW00E8 to SW00EF).
Depending on the link refresh timing, the update of 'Station type match status'
(SW00E8 to SW00EF) may be offset by one sequence scan.
Availability
Master
Local station
station
Unicast
mode
Appendix 4 List of Link Special Relay (SB)
Multicast
mode
*1
A
*1
*1
*1
*1
APPX