Communication period setting value (protocol version 2.0)
■Communication cycle interval (calculation value) (Un\G1277444)
Stores the communication cycle intervals that are calculated by the number of slave stations and the number of link device
points set in "Network Configuration Settings" under "Basic Settings".
Stores the communication cycle interval of protocol version 2.0 regardless of the setting value of 'Protocol setting'
(Un\G1294018). When 'Protocol setting' (Un\G1294018) is set to '1: Protocol version 1.0 fixed', if devices supporting protocol
version 1.0 and devices supporting protocol version 2.0 are mixed, refer to the value in this buffer memory, and set the
appropriate value to "Communication Period Interval Setting" in "Communication Period Setting" under "Basic Settings".
• 125 or greater: Communication cycle intervals (unit: s)
■Cyclic transmission time (calculation value) (Un\G1277445)
Stores the cyclic transmission times that are calculated by the number of slave stations and the number of link device points
set in "Network Configuration Settings" under "Basic Settings".
Stores the cyclic transmission times of protocol version 2.0 regardless of the setting value of 'Protocol setting' (Un\G1294018).
When 'Protocol setting' (Un\G1294018) is set to '1: Protocol version 1.0 fixed', if devices supporting protocol version 1.0 and
devices supporting protocol version 2.0 are mixed, refer to the value in this buffer memory, and set the appropriate value to
"Communication Period Interval Setting" in "Communication Period Setting" under "Basic Settings".
• 1 or greater: Cyclic transmission time (unit: s)
■Transient transmission time (calculation value) (Un\G1277446)
Stores the transient transmission times that are calculated by the number of slave stations and the number of link device
points set in "Network Configuration Settings" under "Basic Settings".
Stores the transient transmission times of protocol version 2.0 regardless of the setting value of 'Protocol setting'
(Un\G1294018). When 'Protocol setting' (Un\G1294018) is set to '1: Protocol version 1.0 fixed', if devices supporting protocol
version 1.0 and devices supporting protocol version 2.0 are mixed, refer to the value in this buffer memory, and set the
appropriate value to "Communication Period Interval Setting" in "Communication Period Setting" under "Basic Settings".
• 1 or greater: Transient transmission time (unit: s)
CC-Link IE TSN Communication Software information
Information related to the CC-Link IE TSN Communication Software is stored.
■CC-Link IE TSN Communication Software information (1st module) (Un\G1277456 to
Un\G1277479)
Address
Un\G1277456
Un\G1277457
Un\G1277458
Un\G1277459
Un\G1277460
Un\G1277461
Un\G1277462 to Un\G1277464
Un\G1277465, Un\G1277466
Un\G1277467 to Un\G1277474
Un\G1277475 to Un\G1277479
APPX
258
Appendix 3 Buffer Memory
Name
Manufacturer code
Model type
Model code (lower 2 bytes)
Model code (upper 2 bytes)
Model code of extension module
Version
MAC address
IP address (IPv4)
IP address (IPv6)
System area
Description
Information of the CC-Link IE TSN Communication
Software in the 1st module is stored.