Interlink Transmission Settings
Set link device ranges when cyclic data are transferred from a station in the own network to a station in a different network.
Setting method
The procedure for the interlink transmission settings is shown below.
1.
Select combination of modules in the "Transfer Source Module" and "Transfer Destination Module" boxes and enter
setting values.
2.
Click the [OK] button to finish the interlink transmission settings.
Item
Description
Transfer Source Module
Select the combination of transfer source and transfer destination modules.
Transfer Destination
Module
Setting method
Right-click in the "Interlink Transmission Parameters" window and select a link device setting method
from the "Setting Method" menu.
• Start/End: Enter the start and end numbers of link devices.
• Points/Start: Enter the numbers of points and start numbers of link devices.
RX/LB
Source
Enter the link device range of the transfer source and destination modules. Up to 64 interlink
LB/RY
transmission ranges can be set. RX and RY points can be assigned in increments of 16 (Start: 0H,
Destination
End: FH).
RX
RX
RX
No.1
LB
No.2
LB
·
·
·
No.64
LB
No.1
LB
RY
No.2
RY
LB
·
·
·
No.64
RY
LB
Setting range
The setting varies
depending on the set
module.
• Start/End
• Points/Start
(Default: Start/End)
RX: 0H to 3FFFH
RY: 0H to 3FFFH
(Default: empty)
2 PARAMETER SETTINGS
2.4 Application Settings
2