*1 When the settings cannot be determined with the module parameter and "Network Configuration Settings", a hyphen or incorrect
calculation result may be displayed.
*2 This setting can be used for the firmware version "10" or later. When "Synchronous" is set for a firmware version that is not supported,
an error occurs in the RJ71GN11-T2.
*3 When the "CC-Link IE TSN Class" of the general CC-Link IE TSN module added to the list of stations under network configuration
setting is CC-Link IE TSN Class A, when the minimum value for the communication cycle interval and cyclic transmission time are set to
"Communication Period Interval Setting" and "Cyclic Transmission Time", cyclic transmission may not be possible. In this case, select
the actual devices to be used from "Module List" and add it to the list of stations, or check the maximum response time during time-
managed polling using the manuals of the devices used, and calculate and set the communication cycle interval and cyclic transmission
time.
*4 If the number of points of the assigned link device exceeds the number of points that can be assigned to the CC-Link IE TSN Class in
the CC-Link IE TSN Class A station, an link device number of points error occurs (error code: 3160H). For the number of points that can
be assigned to CC-Link IE TSN Class A slave stations, refer to the following.
Page 120 Number of link devices that can be assigned to a CC-Link IE TSN Class A slave station
*5 If "Subnet Mask" is set in "Station No./IP Address Setting" of "Required Settings", the same value is set as default.
Because a portion of the setting items are not displayed in simple display, when there are deficiencies in
setting items that are not displayed, the "Output" window may display a warning or error by selecting [Close
with Reflecting the Setting].
If a warning is displayed, switch to detailed display and correct the items.
■Number of link devices that can be assigned to a CC-Link IE TSN Class A slave station
The number of points of link devices assigned to a CC-Link IE TSN Class A slave station must satisfy the following two
conditional formula.
• (Number of points of "RY Setting"  8) + (Number of points of "RWw Setting"  2)  1912
• (Number of points of "RX Setting"  8) + (Number of points of "RWr Setting"  2)  1872
2 PARAMETER SETTINGS
120
2.5 "CC-Link IE TSN Configuration" Window