Multicast mode (1Gbps)
■Calculation formula
Communication cycle interval [ns] = 
that are less than 1s.
sp
Cyclic transmission time [ns] = 
• 
: This value varies depending on whether a CC-Link IE TSN Class A slave station with the basic cycle or normal speed
c
cycle exists or not.
Item
When a CC-Link IE TSN Class A slave station with the basic cycle or normal
speed cycle does not exist
When a CC-Link IE TSN Class A slave station with the basic cycle or normal
speed cycle exists
*1
No.
Calculation formula
1
A1+A2+(the value obtained by the calculation
formula in No.3 or No.4, whichever is larger)
2
B1+B2+(the value obtained by the calculation
formula in No.3 or No.4, whichever is larger)
3
C1+C2
4
D1+D2
5
En7
6
The largest value among the maximum response times during the time-managed polling of the CC-Link IE TSN Class A slave stations set in the basic
cycle or medium speed cycle
*1 The symbols in the table are as follows.
A1, B1, C1, D1: Main module calculation formula
A2, B2, C2, D2: Extension module calculation formula
For the maximum response time for time-managed polling for the slave stations, refer to the user's manual for
the slave station used.
• 
: The calculation formula is as follows.
sc
Calculation formula
{(30  (sn1r+sn1l))+(16  (sn2r+sn2l))+(sndmr+sndml)}  4+(1661  (sn1r+sn1l))
Cyclic processing time [ns]=
• 
: p1+p2+p3+kp+kum
p
• 
: p4
sp
■Variable
For each variable to be used, round it up to one decimal point before assigning to the calculation formula.
Name of variable
Description
(ndmr + (16  n2r))/1488 or Rn, whichever is larger
n1r
Round up the calculated value to the nearest integer of (ndml+(16  n2l))/1488
n1l
(sndmr + (16  sn2r))/1488 or SRn, whichever is larger
sn1r
Round up the calculated value to the nearest integer of (sndml+(16  sn2l))/1488
sn1l
n2r
Rn(RYrb+RWwrb)
RYrb: Value of (Total number of points of "RY setting" set in the remote station (main modules))/(11776  Rn) rounded up to the
nearest integer
RWwrb: Value of (Total number of points of "RWw setting" set in the remote station (main modules))/(736  Rn) rounded up to the
nearest integer
+ 
+ 
+ 
or 125000, whichever is larger. Round up values of 
c
p
sc
sp
+ 
c
sc
A1: {(50(n1r+n1l))+(16(n2r+n2l))+(ndmr+ndml)}8+(Sn-1)830+14000+nh+nrp
A2: {(50en1r)+(16en2r)+endmr}8
B1: {(30(n1r+n1l))+(16(n2r+n2l))+(ndmr+ndml)}4+(1661(n1r+n1l))+(Sn-1)830+14300+nh+nrp
B2: {(30en1r)+(16en2r)+endmr}4+(1661en1r)
C1: {(50n3)+(20n4)+nds}8+14000+nh
C2: {(50en3)+(20en4)+ends}8
D1: {(50n5)+(20n6)+ndl}8+(Sn-1)830+14000+nh
D2: {(50en5)+(20en6)+endl}8
E: (Sn-1)830+39102
+
p
sp
Calculation formula
The larger of No.1 or No.2 + No.5
The larger of No.1 or No.2 + No.5 + No.6
, 
, 
, and
c
p
sc
APPX