Error
Error definition and causes
code
D27BH
The IP address set in the UINI instruction is
incorrect.
D27CH
The network topology setting of the
CCPASET instruction is incorrect.
D27FH
The own station IP address specified in the
control data is not set.
D2C0H
The network number setting of the
CCPASETX instruction executing station is
incorrect.
D2C1H
The station type and station number of the
CCPASETX instruction executing station are
incorrect.
D2C5H
The IP address of the CCPASETX
instruction is incorrect.
D2C6H
The slave station communication cycle
setting of the CCPASETX instruction is
incorrect.
D2C7H
The number of occupied stations specified in
the CCPASETX instruction is incorrect.
D2C8H
The station type of the CCPASETX
instruction is incorrect.
D2C9H
The station number setting of the
CCPASETX instruction is incorrect.
D2CAH
The total number of slave stations specified
in the CCPASETX instruction is incorrect.
D2CBH
The network topology setting of the
CCPASETX instruction is incorrect.
D2CCH
The disconnection detection setting of the
CCPASETX instruction is incorrect.
D2CDH
The communication mode of the CCPASETX
instruction is incorrect.
D2CEH
The communication cycle setting of the
CCPASETX instruction is incorrect.
4 TROUBLESHOOTING
224
4.5 List of Error Codes
Action
• Execute the instruction again after correcting the IP address in the control
data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Correct the network topology setting in the control data, and retry the
operation.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Execute the UINI instruction, and execute the CCPASETX instruction.
Set "Network No." under "Network No." of "Required Settings" to between 1
and 239.
Rewrite the module parameter using the engineering tool. If the same error
occurs again even after taking the above, the possible cause is a hardware
failure of the error module. Please consult your local Mitsubishi
representative.
• Execute the instruction again after correcting the IP address of the slave
station in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the communication cycle
setting of the slave station in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the number of occupied
stations in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the station type in the
network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• When "Station Type" in the network configuration setting data is set to
"Master Station", correct "Station Number" to 0 and when "Station Type" is
set to the type other than "Master Station", correct "Station Number" to a
value within 1 to 120. Then, execute the instruction again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the total number of slave
stations in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the network topology setting
in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the disconnection detection
setting in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the communication mode in
the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting "Setting in Units of 1s",
"Communication Period interval setting", "System Reservation time",
"Cyclic Transmission time", "Normal-Speed", and "Low-Speed" in the
communication cycle setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Detailed
information 1
Detailed
information 2