Particulate And Gaseous Contamination Specifications - Dell EMC PowerEdge MX7000 Field Service Manual

Hide thumbs Also See for EMC PowerEdge MX7000:
Table of Contents

Advertisement

Expanded operating range
● The operating temperature is specified for a maximum altitude of 950 m for expanded operating range.
● Do not perform cold start at 5°C or lower, due to hard drive constraints.
● Redundant power supplies are required.
Expanded operating temperature restrictions
For more information about the expanded operating temperature restrictions, see the Installation and Service Manual for the
PowerEdge MX sleds at www.dell.com/poweredgemanuals.
Table 47. Expanded operating temperature restrictions 
System
Dell EMC PowerEdge
MX7000 including the fans,
Management Module, and
PSUs
Fabrics A and B modules
Fabric C I/O modules

Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any damages to the IT equipment and/or failure from particulates
and gaseous contamination: If the levels of particulates or gaseous pollution exceed the specified limitations and result in
equipment damage or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is
the responsibility of the customer.
Table 48. Particulate contamination specifications  
Particulate
Specifications
contamination
Air Filtration
Data center air filtration defines that, ISO Class 8 per ISO 14644-1 with a 95% upper confidence limit.
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
● Air must be free of corrosive dust.
Corrosive dust
● Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
Table 49. Gaseous contamination specifications  
Gaseous
Specifications
contamination
Copper Coupon
<300 Å/month per Class G1 defines that, ANSI/ISA71.04-1985.
Corrosion
Silver Coupon
<200 Å/month defines that, AHSRAE TC9.9.
Corrosion
C30
No restrictions
No restrictions
No restrictions
NOTE:
This condition applies to data center environments only. Air filtration requirements do not
apply to IT equipment designed to be used outside a data center, in environments such as an office
or factory floor.
NOTE:
Air entering the data center must have MERV11 or MERV13 filtration.
NOTE:
This condition applies to data center and nondata center environments.
NOTE:
This condition applies to data center and nondata center environments.
C35
No restrictions
No restrictions
No restrictions
C40E45
No restrictions
The MX9116n is not
supported.
No restrictions
Technical specifications