1. CONNECTION CONFIGURATION

4.1.11 Ethernet connection

System configuration
Target device
QCPU
QSCPU
QnA/ACPU
Motion controller
*1 *3
CPU(Q series)
Ethernet
Motion controller
CPU(A series)
*1 *2
CNC C70
*1
10BASE-T cable
CRnQ-700
100BASE-TX cable
MELSECNET/H
remote I/O
*3
station
A
J61QBT11
C
Ethernet
module
*1: Configure the multiple CPU system.
*2: Connecting to Display I/F
*3: GT SoftGOT1000 is not available.
*4: Use a cable that supports an Ethernet module and Ethernet board/card to be used.
*5: For available Ethernet boards/cards, refer to the following page.
Available module
CPU series
MELSEC-Q series (Q mode)
MELSEC-QS series
MELSEC-QnA series
MELSEC-Q series (A mode)
MELSEC-A series
Motion controller CPU (A series)
162
4.1 MITSUBISHI Programmable Controller
4.1.11 Ethernet connection
cable
Communication unit
Not required
Built in GOT
Ethernet
Not required
*4
Built in personal
computer
Commercially-available
Ethernet board
Programmable
controller CPU
QJ71E71-100
QJ71E71-B5
QJ71E71-B2
QJ71E71
AJ71QE71N3-T
AJ71QE71N-B5
AJ71QE71N-B2
AJ71QE71N-T
AJ71QE71N-B5T
AJ71QE71
AJ71QE71-B5
AJ71E71N3-T
AJ71E71N-B5
AJ71E71N-B2
AJ71E71N-T
AJ71E71N-B5T
AJ71E71-S3
GT15-J71E71-100
DOS/V
personal
computer
GOT
PC CPU
module
GT SoftGOT1000
License key for
GT SoftGOT1000
*6: The number of total GT SoftGOT 1000 running in personal computer is included.
*7: Connect the PC CPU module to another programmable controller.
*8: When connecting GT16 to an equipment that meets the 10BASE (-T/2/5)
standard, use the switching hub and operate in an environment where
10Mbps and 100Mbps can be mixed.
Ethernet module
GOT
*8
Max. number of
GOTs connected
128
GT16
(16 units or less
are recommended.)
Max. connection
distance
Max. segment length
100 m
GT15
Max. number
of personal
computers
connected
128
(16 units or less
are recommended.)
GT SoftGOT1000
Max. connection
+
distance
License key for
Max. segment length
GT SoftGOT1000
100 m
Max. number
of personal
computers
connected
128
(16 units or less
are recommended.)
+
Max. connection
distance
Max. segment length
100 m
*9
A1SJ71QE71N3-T
A1SJ71QE71N-B5
A1SJ71QE71N-B2
A1SJ71QE71N-T
A1SJ71QE71N-B5T
A1SJ71QE71-B5
A1SJ71QE71-B2
A1SJ71E71N3-T
A1SJ71E71N-B5
A1SJ71E71N-B2
A1SJ71E71N-T
A1SJ71E71N-B5T
A1SJ71E71-B5-S3
A1SJ71E71-B2-S3

Advertisement

Table of Contents
loading

Table of Contents