Dialer Abort Delay (02006) - GE Concord 4 Series Installation Instructions Manual

Security systems
Hide thumbs Also See for Concord 4 Series:
Table of Contents

Advertisement

Auto Phone Test (02001)
This setting determines if the panel sends a phone test automatically to the
central station or a pager on a predetermined schedule. (Refer to the
"Phone Test Freq." and "Next Phone Test" settings found under
).
GLOBAL
Note
For UL 1610 & 1635 listed installations, this feature must be set to on.
Auto Test Reset (02002)
This setting determines whether or not the Auto Phone Test interval is reset after
any successful report to the central monitoring station. (Refer to the "Phone Test
Freq." and "Next Phone Test" settings found under
When this feature is on, the panel considers any successful report to the central
monitoring station to be a successful phone test. Thus, any panel report resets the
Next Phone Test setting to the Phone Test Freq. value. The panel only conducts an
Auto Phone Test if no other reports have been made during the Phone Test Freq.
time period.
Note
Phone Test Freq must be set to 2 or higher for Auto Test Reset to work.
When this feature is off, an Auto Phone Test is always conducted according to the
schedule of the Phone Test Freq. setting, even if the panel makes other reports to
the central monitoring station during that time period.
Comm Failure (02003)
This setting determines whether the panel activates trouble beeps to alert users on
the premises that communication to the central station failed. Failure notification
occurs after the third unsuccessful reporting attempt to the central station/pager.
Failure notification can occur immediately if inadequate phone line voltage is
detected upon the initial dialing attempt.
Note
For UL Listed installations, Comm Failure must be turned on.
DTMF Dialing (02004)
This setting determines whether the panel uses DTMF tones (on) or
pulse (off) for dialing programmed phone numbers.

Dialer Abort Delay (02006)

This setting determines how much time the user has to abort a panel
alarm report.
Note
For UL Listed systems, the combined time for the Entry Delay and Dialer
Abort Delay must not exceed 60 seconds.
Concord 4 Series Systems
TIMERS—GLOBAL
WWW.DIYALARMFORUM.COM
Phone Options-Global (Default = off)
To turn Automatic Phone Test off or on:
1.
With the display showing
TIMERS—
(current setting), press 1 (off) or 2
OFF/ON
(on). The display flashes the entered setting.
2.
Press # and the display shows the new set-
ting.
Phone Options-Global (Default = on)
To turn Auto Test Reset off or on:
1.
With the display showing
).
RESET OFF/ON
1 (off) or 2 (on). The display flashes
the entered setting.
2.
Press
setting.
Phone Options-Global (Default = on)
To turn Communication Failure notifi-
cation off or on:
1.
With the display showing
FAILURE OFF/ON
press 1 (off) or 2 (on). The display
flashes the entered setting.
2.
Press # and the display shows the
new setting.
Phone Options-Global (Default = on)
To turn DTMF Dialing off or on:
1.
With the display showing
(current setting), press 1 (off) or 2 (on).
ON
The display flashes the entered setting.
2.
Press # and the display shows the new setting.
Phone Options-Global (Default = 30 sec.)
To change the Dial Abort Delay:
1.
With the display showing
(current setting), enter the desired time
nn SECS
(15–45). The display flashes the entered set-
ting.
2.
Press # and the display shows the new setting.
AUTO PHONE TEST
AUTO TEST
(current setting), press
# and the display shows the new
COMM
(current setting),
DTMF DIALING OFF/
DIAL ABORT DELAY
36