Household Fire Warning System (Ul 985); Ul 1023 & 985 24-Hour Backup; Sia System Requirements; Sia Setting Requirements - GE Concord 4 Series Installation Instructions Manual

Security systems
Hide thumbs Also See for Concord 4 Series:
Table of Contents

Advertisement

Note
UL requirements take prior-
ity over SIA requirements.
Shortcut #
Function
0013 - 0063
Exit Extension
0016 - 0066
Duress Code
02006
Dialer Abort Delay
02007
Cancel Message
02009
Call Wait Cancel
0310 - 0360
Entry Delay
0311 - 0361
Exit Delay
06015
Swinger Limit
1100
Smoke Verify
N/A
Cross Zoning
Concord 4 Series Systems

Household Fire Warning System (UL 985)

Basic system, plus:
Hardwire Smoke Detector: System Sensor models 2400 or 2400TH learned into sensor group
26 or Sentrol (ESL) models 429AT, 521B or 521BXT learned into sensor group 26
Wireless Smoke Sensor 60-506-319.5 or 60-848-02-95 learned into sensor group 26
Immediate Beeps set to on
UL 98 Options set to on
Receiver Failure set to on (if wireless devices are used)
Siren Verify set to on
RF TX Timeout set to 4 hours (if system includes a built in receiver or SuperBus 2000 RF
Transceiver and wireless smoke sensors)
Sleep Time set to off
Siren Timeout set to 4 minutes or more
Two Trip Error set to off
Disable Trouble Beeps set to off
UL 1023 & 985 24-Hour Backup
For 24-hour backup, the total current draw for all connected devices is limited to 90 mA (during
normal standby conditions) using a 4.5 Ah battery, or 190 mA (during normal standby condi-
tions) using a 7.0 Ah battery.

SIA System Requirements

SIA system requirements are the same as those described for a UL Listed Basic System on page
1, plus:
If multiple annunciation is required, use additional touchpads. Model numbers 60-746-01,
60-803, 60-804, 60-820, 60-983, 60-984, 60-985.

SIA Setting Requirements

The following table describes programming requirements to meet ANSI-SIA CP-01.
Programming
Page
Reference
29
30
35
36
36
40
40
46
58
91
WWW.DIYALARMFORUM.COM
Testing
Default
Page
Setting
Reference
70
On
70
Disabled
70
30 Sec.
70
On
70
Disabled
70
30 sec.
70
60 sec.
70
1
70
Off
70
Disabled
Required Setting
On
Disabled
15-45 sec.
On
On if reporting to central station and
customer has call waiting service
30-240 sec.
45-184 sec.
1
On if smoke alarms are programmed
into system
Enabled for zones with a high
probability of false alarms
2