F216
RX Reference 1
Program  Frequency Settings
This parameter is used to set the gain and bias of the RX input terminal when the
RX terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.
This parameter sets the RX input level that is associated with
when operating in the Speed Control mode or is associated with the
Reference 1
when operating in the Torque Control mode.
RX Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input at
the RX input terminal:
• Program  Utility Group  Frequency Mode 1  RX.
• Program  Utility Group  Command Mode  Terminal Block.
Speed Control
Perform the following setup to allow the system to perform Speed control from
the RX input terminal:
• Set
RX Frequency 1
(F217).
• Set
RX Reference 1
(F216) — the input analog signal level that corresponds
to the speed setting at
• Set
RX Frequency 2
(F219).
• Set
RX Reference 2
(F218) — the input analog signal level that corresponds
to the speed setting at
• Provide a Run command (F and/or R).
Once set, as the RX input voltage changes, the ASD output speed and/or torque
will vary in accordance with the above settings.
This parameter value is entered as -100% to +100% of the RX input signal range.
See parameter
F474
and
F475
response.
RX Frequency 1
Program  Frequency Settings
This parameter is used to set the gain and bias of the RX input terminal when the
RX terminal is used as the control input while operating in the Speed Control
mode.
This parameter sets
RX Frequency 1
the setting of
RX Reference 1
See RX Reference 1 (F216) for more information on this setting.
90
RX Frequency
1.
RX Frequency
2.
for information on fine-tuning this terminal
and is the frequency that is associated with
when operating in the Speed Control mode.
Direct Access Number — F216
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — -100
Maximum — +100
RX Frequency 1
RX Torque
Units — %
Direct Access Number — F217
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Q9 ASD Installation and Operation Manual
F217
Frequency Settings