Toshiba Q9 Installation And Operation Manual page 184

Asd
Table of Contents

Advertisement

F933
My Function Count Data 1
Program  My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output COUNT1 (ON Timer).
COUNT1 (ON Timer) outputs a 1 upon reaching the threshold setting at this
parameter.
My Function Count Data 2
Program  My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output COUNT2 (ON Timer).
COUNT2 (ON Timer) outputs a 1 upon reaching the threshold setting at this
parameter.
Input Function Target 1
Program  My Function Unit 4
This parameter plays a role in the setup of the My Function feature by selecting
the functionality of the programmable Input Function Target 1 terminal.
This setting assigns the function of the programmable Input Function Target 1
terminal to any of the user-selectable functions listed in
7 on pg.
190, or
Table 8 on pg.
See
F977
for more information on this parameter.
Input Function Command 1
Program  My Function Unit 4
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/reset function.
Table 9 on pg. 194
lists the available selections. Their use and selection
requirements are described in an example at F977.
Input Function Target 2
Program  My Function Unit 4
This parameter plays a role in the setup of the My Function feature by selecting
the functionality of the programmable Input Function Target 2 terminal.
This setting assigns the function of the programmable Input Function Target 2
terminal to any of the user-selectable functions listed in
7 on pg.
190, or
Table 8 on pg.
See
F977
for more information on this parameter.
Input Function Command 2
Program  My Function Unit 4
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/reset function.
Table 9 on pg. 194
lists the available selections. Their use and selection
requirements are described in an example at F977.
174
Table 5 on pg.
192.
Table 5 on pg.
192.
Direct Access Number — F933
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 9999
Units — Pulses
Direct Access Number — F934
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 9999
Units — Pulses
Direct Access Number — F935
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
188,
Table
Direct Access Number — F936
Parameter Type — Selection List
Factory Default — 0 (NOP)
Direct Access Number — F937
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
188,
Table
Direct Access Number — F938
Parameter Type — Selection List
Factory Default — 0 (NOP)
Q9 ASD Installation and Operation Manual
F938