F205
V/I Torque Reference 1
Program  Frequency Settings
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Torque
Control mode.
V/I Input Torque Control Setup
Perform the following setup to allow the system to receive Torque Control input
at the V/I input terminal:
• Set SW301 of the Terminal Board to Voltage if using a control voltage or to
Current if using a control current (see
• Program  Utility Group  Frequency Mode 1  V/I.
• Program  Utility Group  Command Mode  Terminal Block.
Torque Control
Perform the following setup to allow the system to perform Torque Control from
the V/I input terminal:
• Set
V/I Torque Reference 1
• Set
V/I Reference 1
(F201) — the input analog signal level that corresponds
to the torque setting at
• Set
V/I Torque Reference 2
• Set
V/I Torque Reference 2
corresponds to the torque setting at
• Provide a Run command (F and/or R).
Torque Control is accomplished by establishing an associated V/f output pattern
for a given V/I input level.
Once set, as the V input voltage changes or the I input current changes, the output
torque of the ASD will vary in accordance with the above settings.
This parameter sets
V/I Torque Reference 1
associated with the setting of
Control mode.
This value is entered as 0% to 250% of the rated torque.
Note:
When using the isolated V/I input terminal the IICC terminal must
be used as the return (Negative) connection.
V/I Torque Reference 2
Program  Frequency Settings
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Torque
Control mode.
Torque Control is accomplished by establishing an associated V/f output pattern
for a given V/I input level.
This parameter sets
V/I Torque Reference 2
associated with the setting of
Control mode.
This value is entered as 0% to 250% of the rated torque.
See V/I Torque Reference 1 (F205) for more information on this setting.
Q9 ASD Installation and Operation Manual
Figure 9 on pg.
(F205).
V/I Torque Reference
1.
(F206).
(F203) — the input analog signal level that
V/I Torque Reference
and is the output torque value that is
V/I Reference 1
when operating in the Torque
and is the output torque value that is
V/I Reference 2
when operating in the Torque
Direct Access Number — F205
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
22).
2.
Direct Access Number — F206
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
F206
Torque Settings
85