F741
Trace Cycle
No Path — Direct Access Only
This parameter sets the record time for the Trace Data events selected at
F742
– F745.
Settings:
0 — 4 ms
1 — 20 ms
2 — 100 ms
3 — 1 Second
4 — 10 Seconds
Trace Data 1
No Path — Direct Access Only
This parameter is used to select the Trace Data 1 item to be read and stored from
the setup of parameters
F740
See
F740
for more information on this parameter setting.
Trace Data 2
No Path — Direct Access Only
This parameter is used to select the Trace Data 2 item to be read and stored from
the setup of parameters
F740
See
F740
for more information on this parameter setting.
Trace Data 3
No Path — Direct Access Only
This parameter is used to select the Trace Data 3 item to be read and stored from
the setup of parameters
F740
See
F740
for more information on this parameter setting.
Trace Data 4
No Path — Direct Access Only4
This parameter is used to select the Trace Data 4 item to be read and stored from
the setup of parameters
F740
See
F740
for more information on this parameter setting.
kWH Memory Set
Program Special Controls
This parameter is used to set the disposition of the kWH meter reading at power
off.
Settings:
Save at Power Off
Clear at Power Off
Q9 ASD Installation and Operation Manual
and F741.
and F741.
and F741.
and F741.
Direct Access Number — F741
Parameter Type — Selection List
Factory Default — 100 ms
Changeable During Run — Yes
Direct Access Number — F742
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Direct Access Number — F743
Parameter Type — Selection List
Factory Default — Freq. Reference
Changeable During Run — Yes
Direct Access Number — F744
Parameter Type — Selection List
Factory Default — Output Current
Changeable During Run — Yes
Direct Access Number — F745
Parameter Type — Selection List
Factory Default — DC Voltage
Changeable During Run — Yes
Direct Access Number — F748
Parameter Type — Selection List
Factory Default — Save at Power Off
Changeable During Run — No
F748
151