Toshiba Q9 Installation And Operation Manual page 148

Asd
Table of Contents

Advertisement

F643
Restart Wait Time
Program  Protection
This parameter is used with synchronous motor applications only.
Contact the Toshiba Customer Support Center for information on this
parameter.
Settings:
0 — 10 Hz Over
1 — 20 Hz Over
V/I Input Loss Response
Program  Special Controls
This parameter is used to provide a system disposition in the event of the loss of
the V/I input signal.
The system will either trip or run the speed set at
Note:
Preset Speed 14
must be configured to use the preset speed
selection.
Settings:
Trip
Preset Speed 14
PTC Thermal Detection Disposition
No Path — Direct Access Only
This parameter sets the ASD disposition in the event that the PTC resistance
exceeds the setting of parameter F646.
The RR input terminal becomes the PTC Thermal Input terminal when Alarm
or Trip is selected at this parameter.
This parameter setting overrides the
settings.
Settings:
0 — Do Nothing
1 — Alarm
2 — Trip
PTC Thermal Detection Level
No Path — Direct Access Only
This parameter provides a user-set resistance threshold for the thermal sensor that,
once exceeded, will activate the selection of F645.
138
Preset Speed
14.
Frequency Mode 1
and
Frequency Mode 2
Direct Access Number — F643
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Direct Access Number — F644
Parameter Type — Selection List
Factory Default — Trip
Changeable During Run — No
Direct Access Number — F645
Parameter Type — Selection List
Factory Default — Do Nothing
Changeable During Run — No
Direct Access Number — F646
Parameter Type — Numerical
Factory Default — 3000
Changeable During Run — No
Minimum — 100
Maximum —9999.0
Units — Ω