F416
Stall Prevention Factor 1
No Path — Direct Access Only
This parameter is to be adjusted in the event that the motor stalls when operated
above the base frequency.
If a momentary heavy-load condition occurs the motor may stall before the load
current reaches the stall prevention level setting of F601.
A drop in the supply voltage may cause fluctuations of the load current or may
cause motor vibration. A gradual adjustment of this parameter may alleviate this
condition.
Start with a setting of 85 at these parameters and gradually adjust them from there
one at a time until the desired results are produced.
Adjustments to this parameter may increase the load current of the motor and
subsequently warrant an adjustment at the Motor Overload Protection Level
setting.
Power Running Torque Limit
No Path — Direct Access Only
This parameter determines the source of the control signal for the positive torque
limit setting.
If
F441
is selected, the value set at
Limit input.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F441
(Setting)
Power Running Torque Limit Level
No Path — Direct Access Only
This parameter provides a value for the Power Running Torque Limit setting if
Setting is selected at parameter F440.
This value provides the positive torque upper-limit for the number 1 motor.
Set this parameter to 250% to disable this function.
Regenerative Braking Torque Limit
No Path — Direct Access Only
This parameter determines the source of the Regenerative Torque Limit control
signal.
If
F443
is selected, the value set at
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F443
(Setting)
Q9 ASD Installation and Operation Manual
F441
is used as the Power Running Torque
F443
is used for this parameter setting.
Direct Access Number — F416
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — No
Minimum — 10
Maximum — 250
Direct Access Number — F440
Parameter Type — Selection List
Factory Default
—F441
Setting
Changeable During Run — Yes
Direct Access Number — F441
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F442
Parameter Type — Selection List
Factory Default —
F443
Setting
Changeable During Run — Yes
F442
123