Toshiba Q9 Installation And Operation Manual page 94

Asd
Table of Contents

Advertisement

F203
V/I Reference 2
Program  Frequency Settings
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the V/I input level that is associated with
when operating in the Speed control mode or is associated with the
Reference 2
when operating in the Torque Control mode.
This value is entered as 0% to 100% of the V/I input signal range.
See
V/I Reference 1
for more information on this setting when used for Speed
control.
See V/I Torque Reference 1 (F205) for more information on this setting when
used for Torque Control.
V/I Frequency 2
Program  Frequency Settings
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets
V/I Frequency 2
the setting of
V/I Reference 2
See V/I Reference 1 (F201) for more information on this setting.
84
and is the frequency that is associated with
when operating in the Speed Control mode.
Direct Access Number — F203
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
V/I Frequency 2
V/I Torque
Units — %
Direct Access Number — F204
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz