F401
Motor Slip Gain
Program  Motor Settings
This parameter provides a degree of slip compensation for a given load. A higher
setting here decreases the slip allowed for a given load/ASD output ratio.
Autotuning 2
Program  Motor Settings
This parameter is used to set the degree that the system automatically adjust the
Autotune parameter values as a function of increases in the temperature of the
motor.
Settings:
0 — Off
1 — Self-Cooled Motor Tuning
2 — Forced Air Cooled Motor Tuning
Motor Rated Capacity
Program  Motor Settings
This parameter is used to set the (name-plated) rated capacity of the motor being
used.
Motor Rated Current
Program  Motor Settings
This parameter is used to set the (name-plated) current rating of the motor being
used.
Motor Rated RPM
Program  Motor Settings
This parameter is used input the (name-plated) rated speed of the motor.
Q9 ASD Installation and Operation Manual
Direct Access Number — F401
Parameter Type — Numerical
Factory Default — 70
Changeable During Run — Yes
Minimum — 0
Maximum — 150
Units — %
Direct Access Number — F402
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
Direct Access Number — F405
Parameter Type — Numerical
Factory Default — 0.75
Changeable During Run — Yes
Minimum — 0.1
Maximum — 500.00
Units — kW
Direct Access Number — F406
Parameter Type — Numerical
Factory Default — ASD Dependent
Changeable During Run — Yes
Minimum — 0.1
Maximum — 2000.0
Units — Amps
Direct Access Number — F407
Parameter Type — Numerical
Factory Default — 1730
Changeable During Run — Yes
Minimum — 100
Maximum — 60000
Units — RPM
F407
121