Preset Speed 15
Program  Preset Speeds
This parameter assigns an output frequency to binary number 1111 and is
identified as Preset Speed 15. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
This parameter setting is also used when commanded by the Fire Speed
activation of a discrete input terminal (see
Remote/Local OTF Switching
No Path — Direct Access Only
This parameter Enables/Disables On-The-Fly switching. OTF Switching is used
when switching from Remote to Local while running and a seamless Remote-to-
Local transfer is required.
With this parameter enabled and while operating in the Remote mode, press the
Local/Remote key to transfer control to the Local mode and maintain the same
running speed of the Remote mode of operation.
Settings:
0 — Disabled
1 — Enabled
PWM Carrier Frequency
Program  Utility Group
This parameter sets the frequency of the pulse width modulation signal applied to
the motor.
Note:
When operating in the Vector Control mode the carrier frequency
should be set to 2.2 kHz or above.
Speed Search Selection
Program  Protection
This parameter Enables/Disables the ability of the drive to start into a spinning
motor when the ST – CC connection opens momentarily and is then closed
(Break/Make ST) or after a power interruption (momentary power failure).
Settings:
0 — Off
1 — Enabled (At Power Failure)
2 — Enabled (At Make-Break ST-CC)
3 — Enabled (At Make-Break ST-CC or Power Failure)
4 — Enabled (At Run)
108
F018
for more information on
Table 4 on pg.
186).
Direct Access Number — F294
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Direct Access Number — F295
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F300
Parameter Type — Numerical
Factory Default — ASD-Dependent
Changeable During Run — No
Minimum — 1.0
Maximum — (ASD-Dependent)
Units — kHz
Direct Access Number — F301
Parameter Type — Selection List
Factory Default — Off
Changeable During Run — No
Q9 ASD Installation and Operation Manual