F210
RR Reference 1
Program  Frequency Settings
This parameter is used to set the gain and bias of the RR input terminal when the
RR terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.
This parameter sets the RR input level that is associated with the
setting when operating in the Speed control mode or is associated with the
Torque Reference 1
setting when operating in the Torque Control mode.
Speed Control
Perform the following setup to allow the system to perform Speed control from
the RR input terminal:
• Set
RR Frequency 1
(F211).
• Set
RR Reference 1
(F210) — the input analog signal level that corresponds
to the frequency setting at
• Set
RR Frequency 2
(F213).
• Set
RR Reference 2
(F212) — the input analog signal level that corresponds
to the frequency setting at
RR Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input at
the RR input terminal:
• Program  Utility Group  Frequency Mode 1  RR.
• Program  Utility Group  Command Mode  Terminal Block.
• Provide a Run command (F and/or R).
Once set, as the RR input voltage changes, the output frequency of the ASD will
vary in accordance with the above settings.
This parameter value is entered as 0% to 100% of the RR input signal range.
RR Frequency 1
Program  Frequency Settings
This parameter is used to set the gain and bias of the RR input terminal when the
RR terminal is used as the control input while operating in the Speed Control
mode.
This parameter sets
RR Frequency 1
the setting of
RR Reference 1
See RR Reference 1 (F210) for more information on this setting.
Q9 ASD Installation and Operation Manual
RR Frequency
1.
RR Frequency
2.
and is the frequency that is associated with
when operating in the Speed Control mode.
Direct Access Number — F210
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
RR Frequency 1
RR
Units — %
Direct Access Number — F211
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F211
Frequency Settings
87