On/Off settings
(continued)
Battery settings
12
6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
Submenu
Energy saving
Sleep mode
Remote command
Bypass standby
Automatic battery test
Low battery warning
Restart battery level
Battery charge mode
External battery
Available settings
[Disabled] [100W] ...
[1000W]
If Enabled, UPS will shut
down after 5 minutes of
back-up time, if load is less
than threshold.
[Enabled] [Disabled]
If Disabled, LCD and
communication will turn
OFF immediately after UPS
is OFF.
If Enabled, LCD and
communication stays ON
90 minutes after UPS is
OFF.
[Enabled] [Disabled]
If Enabled, shutdown or
restart commands from
software are authorized.
[Enabled] [Disabled]
Define if output is powered
from Bypass in Standby
mode.
In constant charge mode:
[No test] [Every day] [Every
week] [Every month]
In ABM cycling mode:
[No test] [Every ABM cycle]
[0%] ... [100%]
The alarm triggers when the
set percentage of battery
capacity is reached during
back-up time.
[0%] ... [100%]
If set, automatic restart
will occur only when
percentage of battery
charge is reached.
[ABM cycling] [Constant
charge]
[Auto detection]
[Manual EBM set.]
[Manual battery set.]
[No battery]
Default settings
[Disabled]
[Enabled]
[Enabled]
[Enabled] for 8PX and 9PX
models
[Disabled] for 8KX and 9KX
models
[Every ABM cycle]
[20%]
[0%]
[ABM cycling]
[Auto detection]
Using standard EBM, UPS
detects automatically the
number of EBM connected