Installation requirements

Recommended protective devices and cable cross-sections
1. Recommended upstream protection
Table 1. Recommended upstream protection
UPS model
5594-8PX
(8k VA 3Phase)
5594-9PX
(11k VA 3Phase)
5594-8KX
(8k VA 1Phase)
5594-9KX
(11k VA 1Phase)
2. RISK OF VOLTAGE BACKFEED. The system has its own power source (the battery). Isolate the UPS
and check for hazardous voltage upstream and downstream during lockout-tagout operation. Terminal
blocks might be energized even if the system is disconnected from the AC power source.
3. Although the UPS does not contain anti-backfeed (ABF) relays, some backfeed protection is provided.
For example, if some components are damaged in battery mode, the output voltage may feed back
to the input. In this case, a current transformer (CT) is used to detect the bypass current feedback
voltage. If a current backfeed fault condition is detected, the UPS will terminate the inverter output to
avoid personal injury.
4. Recommended cable cross-sections
), which is secured by two screws.
Normal and bypass AC
inputs not separate
Normal AC input
D curve 50A
D curve 63A
D curve 50A
D curve 63/70A
Separate normal and bypass AC inputs
Normal AC input
D curve 20A
D curve 32A
D curve 50A
D curve 63/70A
Bypass AC input
D curve 50A
D curve 63A
D curve 50A
D curve 63/70A
.
Chapter 3
Installation
25