Table 11. Electrical output
All models
Voltage regulation
Efficiency
Frequency regulation
Frequency
Output overload
Output overload
(Bypass mode)
Voltage waveform
Harmonic distortion
Transfer time
Power factor
Load crest ratio
Table 12. Electrical output connections
Model
5594-8PX, 5594-8KX
5594-9PX, 5594-9KX
Table 13. AC input and output (1Phase models)
AC Input power
AC Output power
64
6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
Normal mode
±1%
> 98% (High Efficiency mode)
> 94.5% for 8-11kVA models
Sync with line ±5% of nominal line frequency
(outside this range: ±0.5% of auto-selected
nominal frequency)
50 or 60Hz, autosensing or configurable as a frequency converter
100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10s
> 150% : load transfers to Bypass mode after 900ms
100-125% : no alarm
125-150% : UPS shuts down after 1 minute
> 150% : UPS shuts down after 1s
Sinewave
< 2% THDV on linear load
< 5% THDV on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility power)
0.9
3 to 1
Output connection
(4) C19 via MBP
5594-8KX
200-240VAC, 50/60Hz, 1ph, 40A max
50/60Hz, 1ph;
200VAC, 8000VA, 7200W, 40.0A;
208VAC, 8000VA, 7200W, 38.5A;
220VAC, 8000VA, 7200W, 36.4A;
Battery mode
±1%
> 91%
±0.5% of auto-selected nominal
frequency
Output cable
Not provided
5594-9KX
200-240VAC, 50/60Hz, 1ph, 50A max
50/60Hz, 1ph;
200VAC, 10000VA, 9000W, 50.0A;
208VAC, 10000VA, 9000W, 48.1A;
220VAC, 11000VA, 9900W, 50.0A;