Figure 10. 8/11k VA 3Phase
(2) cable glands for UPS Input Bypass connection (optional)
Rack kit for 19-inch enclosures -- including square nuts and screws (
Tower and Wall mounting kit (including 2 ears and screws)

Mechanical mounting

For rack installations, mount the MBP to the rail behind an EBM, just below the UPS. For tower installations,
mount the MBP to an EBM.

Connecting the EBM(s)

Note: A small amount of arcing might occur when connecting EBMs. This is normal and will not harm
personnel. Insert the EBM cable into the battery connector quickly and firmly.
Step 1.
Plug the EBM power cable(s) into the battery connector(s). Up to four EBMs can be connected to
the UPS.
Step 2.
Verify that the EBM connections are tight and that strain relief exists for each cable.
Step 3.
Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
Step 4.
Check that the battery circuit breaker is switched to the "I" (on) position.
)
.
Chapter 3
Installation
21