HotSwap MBP connection

Follow the instructions for your specific MBP model.

8/11k VA 1Phase

Step 1.
Remove the top cover
Step 2.
Punch the knockouts of the MBP I/O UPS connection cover
fittings inside.
1. Remove the jumper.
2. Insert the Normal AC cable through the cable
gland.
3. Connect the five cables (for 8PX and 9PX
models) or three cables (for KX models) to the
Normal AC source terminal blocks. Do not
connect anything to the Bypass terminal
blocks.
4. Insert the Output cable through the cable gland.
5. Connect the three cables to the Output terminal
blocks.
6. Put back and secure the terminal blocks cover
with the screws.
7. Tighten the cable glands.
of the MBP I/O UPS connection cover
after removing the 3 screws.
and insert the 2 provided conduit
.
Chapter 4
Power cables connection
31