Normally closed
Terminal wire size rating is 0.32-4 mm
Remote control connection and test
1. Ensure that the UPS is shut down and the utility power is disconnected.
2. Remove the RPO connector from the UPS by loosening the screws.
3. Connect a normally closed volt-free contact between pins 1 and 3 of the connector.
Normally closed
4. Plug the RPO connector into the back of the UPS and fix the screws.
5. Connect and restart the UPS.
6. Open the external remote shut down contact to test the function.
Note: Always test the RPO function before applying your critical load to avoid accidental load loss.
Connectivity card
The UPS Network Management Card allows the UPS to communicate in Ethernet environments. The card
has SNMP and HTTP capabilities as well as monitoring through a Web browser interface. In addition, a
Environmental Monitoring Probe can be attached to obtain humidity, temperature, smoke alarm, and security
information.
Normally open
2
(22-12 AWG).
Contact open: shut down of UPS
To return to normal operation, close the external remote shut down contact and
restart the UPS from the front panel.
.
Chapter 6
Communication
47