Separate Input Source Connection (1Phase Units); Separate Input Source Connection (3Phase Units) - Lenovo RT8.0kVA Installation And User Manual

6u rack or tower ups rt8.0kva and rt11.0va
Hide thumbs Also See for RT8.0kVA:
Table of Contents

Advertisement

Separate input source connection (1Phase units)

Separate input source connection (3Phase units)

1. Remove the jumper.
2. Insert the Normal AC cable through the cable
gland.
3. Connect the three cables to the Normal AC
source terminal blocks.
4. Insert the Bypass AC cable through the cable
gland.
5. Connect the three cables to the Bypass AC
source terminal blocks.
6. Insert the Output cable through the cable gland.
7. Connect the three cables to the Output terminal
blocks.
8. Put back and secure the terminal blocks cover
with the screws.
9. Tighten the cable glands.
1. Remove the jumper.
2. Insert the Normal AC cable through the cable
gland.
3. Connect the five cables to the Normal AC
source terminal blocks.
4. Insert the Bypass AC cable through the cable
gland.
5. Connect the three cables to the Bypass AC
source terminal blocks.
6. Insert the Output cable through the cable gland.
7. Connect the three cables to the Output terminal
blocks.
8. Put back and secure the terminal blocks cover
with the screws.
9. Tighten the cable glands.
Chapter 4
.
Power cables connection
29