Step 3.
Insert the provided conduit with blue color coding
SOURCE conduit fitting.
Note: Take care to leave the conduit end with blue label on opposite side (for connection to UPS).
Step 4.
Connect the 3 wires of this blue color conduit
terminal blocks.
Step 5.
Insert the provided conduit with red color coding
fitting.
Note: Take care to leave the conduit end with red label on opposite side (for connection to UPS).
Step 6.
Connect the 3 wires of this red color conduit
Step 7.
Put back the MBP I/O UPS connection cover
Step 8.
Put back the top cover
Step 9.
Remove the I/O terminal blocks cover of the UPS.
Step 10. Punch the Input and Output knockouts of the UPS I/O terminal block (TB) cover and insert the 2
provided conduit fittings inside.
Step 11. Insert the conduits
cover, following color coding on the conduits and the UPS I/O TB cover: blue for UPS Input; red for
UPS Output.Do not remove the UPS Input Bypass jumper inside the UPS I/O TB cover.
Step 12. Connect the wires of the conduit with blue color coding
terminal blocks of the UPS, and the wires of the conduit with red color coding
terminal blocks.
Note: Refer to "Access to terminal blocks" on page 27 for more information about terminal-block
connections.
Step 13. Connect the MBP detection cable
Step 14. Put back and secure the I/O terminal blocks cover of the UPS.
Step 15. Remove the top cover
Step 16. Punch the knockouts of MBP I/O cover
inside.
Step 17. Insert the Normal AC source cable through the cable gland (or a conduit through the conduit fitting).
32
6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
of the MBP I/O UPS connection cover
and
through the previously mounted conduit fittings of the UPS I/O TB
to the specific UPS connector.
of the MBP I/O cover
and insert cable glands of UPS (or conduit fittings)
, through the TO UPS NORMAL AC
to the TO UPS NORMAL AC SOURCE MBP
, through the FROM UPS OUTPUT conduit
to the FROM UPS OUTPUT MBP terminal blocks.
and secure it with 4 screws on the MBP casing.
and secure it with 3 screws.
to the NORMAL AC SOURCE
after removing the 3 screws.
to the OUTPUT