10.15
I-PD Control (Enable Tracking for primary loop)
(M+P_IPD_T)
M+P_IPD_T
This function block controls values to slowly respond to a change of the setting value without any shocks and outputs the
result (MV) by using the process variable in the proportional term and derivative term. The primary loop can be tracked.
FBD/LD
M+P_IPD_T
PVP
MVD
CASIN_T
Applicable tag type
IPD
Control mode
MAN
■Block diagram
(%)
PVP
(%)
CASIN_T
(Tracking)
*
Indicates bits item.
Setting data
■Input/output variable
Variable
Description
name
PVP
PV input (unit: %)
CASIN_T
Cascade SV input (unit: %) (With tracking) (Indirect
address)
MV output (unit: %)
MVD
10 LOOP CONTROL OPERATION
270
10.15 I-PD Control (Enable Tracking for primary loop) (M+P_IPD_T)
AUT
Engineering
Inverse
value
engineering
conversion
value conversion
CAS
Tag data
SV
CAS
CMV
M+P_IPD_T
Deviation
-
check
Tracking enabled
(Operation constant
TRK=1)
Disable alarm
detection
DVLA (*)
ALM
Recommended range
0 to 100[%]
0 to 100[%]
-999999 to 999999[%]
CSV
IPD
operation
Tracking
(primary loop)
MAN,
AUT,
CMV
Type
Input variable
Input variable
Output variable
MVD
(%)
(ΔMV)
Data type
REAL
DWORD
REAL