■Public variable (operation constant)
Variable
Description
name
PN
Reverse Action/Direct Action
TRK
Tracking Flag
SVPTN_B0
Setting Value (SV) Used
SVPTN_B1
Setting Value (SV) Pattern
*1 When 1 (tracking is executed) is set to the tracking flag, connect CASOUT_T of the primary loop with the input variable CASIN_T.
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 530 ONF3
Processing details
■MV correction
This function block calculates a deviation (DV).
+
Deviation DV
(%)
0
-
MV
100%
Condition
Direct action (PN = 1)
Reverse action (PN = 0)
DV: Deviation (%), HSO: Hysteresis (%), MV: MV output
SV- Engineering range low limit
SV(%)=
Engineering range high limit-Engineering range low limit
PV- Engineering range low limit
PV(%)=
Engineering range high limit-Engineering range low limit
Hysteresis (%) is a percentage to (Engineering range high limit - Engineering range low limit).
10 LOOP CONTROL OPERATION
302
10.22 3 position ON/OFF Control (Enable Tracking for primary loop) (M+P_ONF3_T)
*1
50%
0%
Recommended range
0: Reverse action
1: Direct action
0: Not executed
1: Executed
TRUE: Not used
FALSE: Used
TRUE: Not primary MV
FALSE: Primary MV
Hysteresis HSO(%)
Hysteresis HSO(%)
Hysteresis HSO(%)
Hysteresis HSO(%)
50%
100%
50%
Deviation (DV)
DV (%) = PV (%) - SV (%)
DV (%) = SV (%) - PV (%)
×100
×100
Initial value
Set by
0
User
0
User
TRUE
User
TRUE
User
Hysteresis
HS1(%)
t
Hysteresis
HS1(%)
Data type
INT
INT
BOOL
BOOL