Manual Output (M+M_Mout) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

12.35

Manual Output (M+M_MOUT)

M+M_MOUT
This FB performs manual output combining the functions of M+P_MOUT into a single FB.
FBD/LD
M+M_MOUT
MVN
Applicable tag type
MOUT
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG)*
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable
Description
name
MVN
Output to a module
■Public variable (operation constant)
Variable
Description
name
MOUT_NMAX
Output Conversion High Limit
MOUT_NMIN
Output Conversion Low Limit
12 LOOP TAG
424
12.35 Manual Output (M+M_MOUT)
AUT
CAS
-
-
M+M_MOUT
MOUT function
(M+P_MOUT)*
CMV
Recommended range
Type
MOUT_NMIN to
Output variable
MOUT_NMAX
Recommended range
Initial value
-999999 to 999999
100.0
-999999 to 999999
0.0
CSV
MVN
Data type
REAL
Set by
Data type
User
REAL
User
REAL

Advertisement

Table of Contents
loading

Table of Contents