9.2
Output Processing-1 with Mode Switching (With
Input Addition) (M+P_OUT1)
M+P_OUT1
This FB performs input addition, variation rate & high/low limiter, reset windup, and output conversion processing to an input
value (MV) and outputs a manipulated value. (with integral and anti-reset windup processing)
FBD/LD
M+P_OUT1
MVD
MVN
CASOUT
CASOUT_T
Applicable tag type
BPI, IPD, PID, SPI, 2PID
Control mode
MAN
AUT
■Block diagram
ΔMV=0
AUT,
TRKF=1
CAS,
CSV
(%)
MVD
(ΔMV)
TRKF=0
MAN,
CMV
Tag data
TRKF (*)
INH
AUT,
Secondary
loop tag
MAN,
CMV
SV (%)
CAS,
CSV
*
Indicates bits item.
CAS
M+P_OUT1
Variation
Input
rate high/low
addition
limiter
Disable Alarm detection
MVP
MHA (*)
MLA (*) DMLA (*)
ALM
SV (%) tracking
(When the secondary loop control mode is AUT/MAN/CMV)

9.2 Output Processing-1 with Mode Switching (With Input Addition) (M+P_OUT1)

CMV
Output
Reset
wind-up
conversion
MAN,
AUT,
CMV
CAS,
CSV
TRKF=1
TRKF=0
(%)
MV
CSV
NOR,
OVR
(MV output)
MVN
SIM
SIMOUT
(Simulation output)
CASOUT
(%)
CASOUT_T
(Tracking)