■Public variable (operation constant)
Variable name
Description
IN_NMAX
Input High Limit
IN_NMIN
Input Low Limit
IN_HH
High Limit Range Error
IN_H
High Limit Range Error Reset
IN_L
Low Limit Range Error Reset
IN_LL
Low Limit Range Error
MSET_SVPTN_B0
Setting Value (SV) Used
MSET_SVLMT_EN
SV High/Low Limiter
MSET_DVLS
Large Deviation Alarm Hysteresis
MSET_PN
Reverse Action/Direct Action
*1 When SVPTN_B0 is TRUE, CASIN inputs cannot be used even though the mode is changed to the CAS mode.
■Public variable (others)
• Control mode change processing (MCHG function)
Variable name
Description
MODEIN
Mode Change Signal
E_
Enable Mode Change
*1 Read or write the variables using a program. They are not displayed on "FB Property" of the engineering tool.
■Tag data
For details on tag data that is read or written with this tag FB, refer to the following.
Page 535 SWM
Processing details
This tag FB consists of the following function blocks.
Item
IN function
PHPL function
MSET function
MCHG function
Operation error
An error may occur in a function block that is used in a tag FB. For details on the error, refer to corresponding function blocks.
Recommended range
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
*1
TRUE: Not used
FALSE: Used
TRUE: Execute
FALSE: Not execute
0 to 100
0: Reverse action
1: Direct action
*1
Recommended range
1 to 3, 5
1: MAN
2: AUT
3: CAS
5: CSV
TRUE: Execute
FALSE: Stop
Function block
M+P_IN
M+P_PHPL
M+P_MSET_
M+P_MCHG
Initial value
Set by
100.0
User
0.0
User
102.0
User
100.0
User
0.0
User
-2.0
User
TRUE
User
FALSE
User
0 to 100
User
0 to 1
User
Initial value
Set by
0
User
FALSE
User
Reference
Page 144 M+P_IN
Page 291 M+P_PHPL
Page 179 M+P_MSET_
Page 338 M+P_MCHG
12.38 Manual Setter with Monitor (M+M_SWM_)
Data type
REAL
REAL
REAL
REAL
REAL
REAL
BOOL
BOOL
12
REAL
INT
Data type
INT
BOOL
12 LOOP TAG
433