12.36
Program Setter (M+M_PGS)
M+M_PGS
This FB performs program settings combining the functions of M+P_PGS into a single FB.
FBD/LD
M+M_PGS
MVP
CASOUT
Applicable tag type
PGS
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG)*
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable
Description
name
MVP
MV output (Unit: %)
CASOUT
Cascade output (Unit: %)
■Public variable (others)
• Control mode change processing (MCHG function)
Variable
Description
name
MODEIN
Mode Change Signal
E_
Enable Mode Change
*1 Read or write the variables using a program. They are not displayed on "FB Property" of the engineering tool.
12 LOOP TAG
426
12.36 Program Setter (M+M_PGS)
AUT
CAS
M+M_PGS
PGS function
(M+P_PGS)*
*1
CMV
Recommended range
Type
0 to 100[%]
Output variable
0 to 100[%]
Output variable
Recommended range
Initial value
1 to 5
0
1: MAN
2: AUT
3: CAS
4: CMV
5: CSV
TRUE: Execute
FALSE
FALSE: Stop
CSV
(%)
MVP
(%)
CASOUT
Data type
REAL
REAL
Set by
Data type
User
INT
User
BOOL