12.24
2 position ON/OFF Control (Disable Tracking for
primary loop) (M+M_ONF2)
M+M_ONF2
This FB performs two-position (on/off) control combining the functions of M+P_IN, M+P_PHPL, and M+P_ONF2 into a single
FB.
FBD/LD
M+M_ONF2
PVN
MVP
CASIN
CASOUT
MVB
Applicable tag type
ONF2
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG)*
PVN
IN function
(M+P_IN)*
CASIN
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable
Description
name
PVN
Input from a module
CASIN
Primary loop SV input (Unit: %)
MV output (Unit: %)
MVP
CASOUT
Cascade MV output (Unit: %)
ON/OFF output (turns on at MV 50%)
MVB
12 LOOP TAG
402
12.24 2 position ON/OFF Control (Disable Tracking for primary loop) (M+M_ONF2)
AUT
CAS
PHPL function
(M+P_PHPL)*
CMV
M+M_ONF2
ONF2 function
(M+P_ONF2)*
Recommended range
-999999 to 999999
0 to 100[%]
0 to 100[%]
0 to 100[%]
TRUE: ON
FALSE: OFF
CSV
MVP
MV(%)
CASOUT
MVB
(Bit output)
Type
Data type
Input variable
REAL
Input variable
REAL
Output variable
REAL
Output variable
REAL
Output variable
BOOL