Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 331

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Loop stop processing
When the stop alarm (SPA) of the alarm (ALM) is TRUE, this function block performs the following processing.
• Outputs (MVN) are held.
• The control mode is automatically switched to MANUAL.
• When DMLA, MHA, or MLA of the alarm (ALM) has occurred, the DMLA, MHA, or MLA is reset.
• No alarm is detected in the variation rate & high/low limiter processing.
■Tracking processing
The following table shows whether tracking processing to the input variable CASIN_T is performed or not.
Condition
Tracking Flag (TRK)
1
0
■Processing operation
: Performed, : Not performed
Control mode
Processing operation
Engineering value
conversion
MAN, CMV
AUT, CAS, CSV
*1 Tracking is performed when the tracking flag (TRK) is 1.
*2 Tracking is performed when the tracking flag (TRK) is 1 and DMLA, MHA, or MLA of the alarm (ALM) has occurred.
*3 An alarm whose corresponding bit is TRUE (Valid) in the disable alarm detection (INH) is not detected.
Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Input data 1 (PVP), operation constant (NMAX, NMIN), tag data, or input data 2 (CASIN_T) is a subnormal number or NaN (not a
number).
3403H
An overflow has occurred.
Result
The input variable CASIN_T1 is tracked.
The input variable CASIN_T1 is not tracked.
Variation rate &
Output conversion
high/low limiter
10.27 Loop Selector (Enable Tracking for primary loop only by CASIN_T) (M+P_SEL_T1)
Tracking
Alarm
*1
*3
*2
*3
10 LOOP CONTROL OPERATION
10
329