Summation (Internal Integer Integration) (M+P_Sum2_) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

5.8
Summation (Internal Integer Integration)
(M+P_SUM2_)
M+P_SUM2_
When the integration start signal (START) is TRUE, this function block performs integration processing to the input (IN) and
outputs the result.
Internal integration for the integral part is executed with signed 32-bit integers.
FBD/LD
M+P_SUM2_
START
COMP_
RST_
OUT_D
IN
OUT_R
■Block diagram
Integration start signal
START
TRUE: Start
FALSE: Stop
Integration reset signal
RST_
TRUE: Valid
FALSE: Invalid
IN
Setting data
■Input/output variable
Variable
Description
name
START
Integration start signal
RST_
Integration reset signal
IN
Input
COMP_
Integration complete signal
OUT_D
Integration value (integral part) output
OUT_R
Integration value real number output
■Public variable (operation constant)
Variable
Description
name
ILC
Input Low Cut-off Value
A_
Initial value
RANGE
Input Range
HILMT
High Limit Value of Integration
5 CORRECTION OPERATION
86

5.8 Summation (Internal Integer Integration) (M+P_SUM2_)

M+P_SUM2_
Analog integration processing
ΔT/T
T: Input range(hr.3600•min.60•sec.1)
ΔT:Execution cycle(sec.)
≥HILMT
Integration for
integral part
Integration for
decimal part
Recommended range
Type
TRUE: Start
Input variable
FALSE: Stop
TRUE: Valid
Input variable
FALSE: Invalid
-999999 to 999999
Input variable
TRUE: Complete
Output variable
FALSE: Unreached
-2147483648 to 2147483647
Output variable
-2147483648 to 2147483647
Output variable
Recommended range
Initial value
-999999 to 999999
0.0
-999999 to 999999
0.0
1 to 3
1
1: /s
2: /min
3: /hour
1 to 2147483647
1000000
COMP_
OUT_D
OUT_R
Data type
BOOL
BOOL
REAL
BOOL
DINT
REAL
Set by
Data type
User
REAL
User
REAL
User
INT
User
DINT