3. 2. 4
If a trip occurs, you can reset it with panel operation.
For how to reset a trip by other than the operation panel (digital input, etc.), refer to [13. 1].
1
Press the [STOP/RESET] key with the trip displayed.
"CLr" blinks in the main area, and "Reset? (STOP)
key" is displayed on the lower side.
• The backlight is red.
It is white when the setting of the backlight is
changed.
3
2
If you press the [STOP/RESET] key again while
"CLr" is blinking, the trip is reset.
The display on the screen once disappears, and
the screen immediately after power on is dis-
played.
The backlight returns to while.
9
Important
Memo
3. [Basic operation] Operation panel and screen display
How to reset trip
• If the cause of the trip is not eliminated, a trip occurs again even after reset.
• If the trip is caused by overload protection or overheat or when pre-alarm occurs, the trip
cannot be reset.
For details, refer to [13. 1].
• The blinking "CLr" returns to the trip display after few seconds if no operation is performed. The
trip is reset only if you press the [STOP/RESET] key while "CLr" is blinking.
• If you press keys other than the [STOP/RESET], it is considered that reset will not be done, and
the screen returns to trip display.
Screen
3-20
E6582062
Trip
20.0Hz
F
17:20
Standard Mode
CLr
Trip reset ? (STOP-Key)
Setting
Monitor
HELLO
0.75KW- 1.0HP
200V
VFAS3-2007P
R