Toshiba TOSVERT VF-AS3 Instruction Manual page 472

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

Category
Emission
Immunity
(1)
EMC Directive compliance of this inverter
The built-in EMC filter on the input side of this inverter (480 V class) reduces conducted noise
and radiated noise from input cables. The compliance with the EMC Directive is as shown in
the table below.
Inverter type
9
VFAS3-4004PC
VFAS3-4007PC
VFAS3-4015PC
VFAS3-4022PC
VFAS3-4037PC
VFAS3-4055PC
VFAS3-4075PC
VFAS3-4110PC
VFAS3-4150PC
VFAS3-4185PC
VFAS3-4220PC
VFAS3-4300PC
VFAS3-4370PC
VFAS3-4450PC
VFAS3-4550PC
VFAS3-4750PC
VFAS3-4900PC
9. Measures to satisfy standards
Subcategory
Radiated noise
Conducted noise
Electrostatic discharge
Radio-frequency electromagnetic field
Electrical fast transient/burst
Surge
Conducted radio-frequency common
mode
Voltage dips, short interruptions and
voltage variations
Carrier
IEC61800-3 category C2
frequency
(EN55011 classB Group1)
<F300>
Length of motor connecting cable
(kHz)
4
4
4
4
4
4
4
4
4
4
4
4
4
2.5
2.5
2.5
2.5
Product
standards
IEC61800-3
Conducted noise
(m)
50
50
50
50
50
50
50
50
50
50
50
50
50
-
-
-
-
9-2
E6582062
Test standard
CISPR11 (EN55011)
CISPR11 (EN55011)
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
IEC61000-4-6
IEC61000-4-11
Conducted noise
IEC61800-3 category C3
(EN55011 classB Group1)
Length of motor connecting cable
(m)
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150

Hide quick links: