Toshiba TOSVERT VF-AS3 Instruction Manual page 164

High-performance industrial inverter for 3-phase motors, 3-phase 240v class 0.4 to 55kw, 3-phase 480v class 0.4 to 280kw
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

9
Select <CMOd: Run command select> and press
the [OK] key.
The setting screen is displayed.
10 Select "0: Terminal" and press the [OK] key.
The basic parameter screen is displayed.
Check that the setting value of <CMOd: Run
4
command select> is "0."
11 Select <Sr1: Preset speed 1> and press the [OK]
key.
The setting screen is displayed.
The default setting is 0.0 Hz.
9
12 Change the setting value with the touch wheel.
When the setting value is changed, the value on
the screen is highlighted.
In the example on the right, it is set to 20.0Hz. This
is the frequency command value of Preset speed 1.
4. [Basic operation] Operation methods of motor
: Run command select
CMOd
: Frequency command select 1
FMOd
: V/f Pattern
Pt
: Manual torque boost 1
vb
: Base frequency 1
vL
CMOd :Run command select
0: Terminal
1: Operation panel,Ext panel
2: Embedded Ethernet
3: RS485 com (connector 1)
4: RS485 com (connector 2)
Sr1
:Preset speed 1
Min: 0.0
X1000
Sr1
:Preset speed 1
Min: 0.0
X1000
4-40
E6582062
STOP
0.0Hz
15:51
Basic parameters
1
10
0
4.80%
60.0Hz
STOP
0.0Hz
F
R
15:51
STOP
0.0Hz
F
R
15:58
0.0
Hz
Max: 60.0
X100
X10
X1
STOP
0.0Hz
F
R
15:58
20.0
Hz
Max: 60.0
X100
X10
X1