■ With frame size A2
VFAS3-2037P, VFAS3-4055PC, 4075PC
1
Remove the front cover.
For how to remove, refer to [2. 2. 1].
2
Remove two screws for switching of grounding
capacitor.
The grounding capacitor is disconnected.
Insert the removed screws to the positions shown
in the figure on the right.
3
To recover the shipping state, mount the two
screws for switching of grounding capacitor and
tighten them.
The
grounding
grounded.
4
After switching, mount the front cover.
For how to mount, refer to [2. 2. 1].
• For models with two switching screws, be sure to set both screws to the same side.
Important
capacitor
is
connected
2-47
Grounding
and
Screw
Non-grounding
E6582062
Screw
10
2. Installation and wiring
2
3
9