 Automatic supervision
 Display of the system quantities on the digest screen
 Display of the fault records on the digest screen
 Display of the automatic monitoring results on the digest screen
The calendar clock can run locally or be synchronized with the external IRIG-B time standard
signal, RSM , IEC or Modbus clock. This can be selected by setting.
If it is necessary to synchronize with the IRIG-B time standard signal, it is possible to transform
GMT to the local time by setting.
When the relays are connected to the RSM system as shown in Figure 4.4.1, the calendar clock of
each relay is synchronized with the RSM clock. If the RSM clock is synchronized with the
external time standard (GPS clock etc.), then all the relay clocks are synchronized with the
external time standard.