CT requirement
The CT knee point voltage Vk is required as follows:
The CT should not be saturated by maximum through fault current.
Vk  (RCT + R1 + Vb/n
Ifm:
Maximum through fault current
N:
CT ratio
RCT:
CT secondary resistance
R1:
CT cable resistance
Vb:
Relay burden
n:
CT secondary rating
2
)  Ifm/N
 210 
6 F 2 S 0 7 8 9