Toshiba GRT100 Series Instruction Manual page 240

Transformer protection relay
Hide thumbs Also See for GRT100 Series:
Table of Contents

Advertisement

No.
Phenomena
2
HMI does not
display IEC103
event on the SAS
side.
3
Time can be
synchronised with
IEC103
communication.
(Note) BCU: Bay control unit, RY: Relay
Supposed causes
The relevant event sending condition is
not valid.
The relevant event Information Number
(INF) and/or Function Type (FUN) may
be different between the relay and SAS.
The relay is not initialised after writing
IEC103 configurator setting.
It changes to the block mode.
BCU does not transmit the frame of time
synchronisation.
The settling of time synchronisation
source is set to other than IEC.
Object
RY
Change the event sending condition (signal
number) of IEC103 configurator if there is a setting
error. When the setting is correct, check the signal
condition by programmable LED, etc.
RY
Match the relevant event Information Number
(INF) or Function Type (FUN) between the relay
SAS
and SAS.
RY
Check the sum value of IEC103 setting data from
the LCD screen. When differing from the sum
value on IEC103 configurator, initialise the relay.
RY
Change the IECBR settling to Normal.
BCU
Transmit the frame of time synchronisation.
RY
Change the settling of time synchronisation source
to IEC.
239
6 F 2 S 0 7 8 9
Check / Confirmation
Procedure