6.5.1.2
2F element
The testing circuit is shown in Figure 6.5.5.
Current
I 1
source
50 or 60Hz
Current
I 2
source
100 or 120Hz
DC
power
supply
DC
voltmeter
The output signal number of the 2F element is as follows:
Set the second harmonic restraint setting k2f to 15%(= default setting).
Press 4 (= Logic circuit) on the "Test" sub-menu screen to display the "Logic circuit"
screen.
Enter a signal number to observe the 2F output at monitoring jack A and press the
ENTER key.
Set the fundamental frequency current I 1 to 3 times of ik setting. Change the magnitude of
the second harmonic current I 2 and measure the value at which the element operates.
Calculate the percentage of the second harmonic by I 2 /I 1 when the element operates.
Check that the percentage is within 7% of the k2f setting.
Figure 6.5.5 Testing 2F Element (Model 100s, 200s)
Element
Signal number
2F
122
119
GRT100
TB 1
-1
I a
-2
Monitoring
jack
TB 4
- A16
- A17
6 F 2 S 0 7 8 9
A
0V