6.4 Hardware Tests
The tests can be performed without external wiring, but DC power supply and AC voltage and
current source are required.
6.4.1
User Interfaces
This test ensures that the LCD, LEDs and keys function correctly.
LCD display
Apply the rated DC voltage and check that the LCD is off.
Note: If there is a failure, the LCD displays the "Auto-supervision" screen when the DC voltage is
Press the RESET key for 1 second and check that black dots appear on the whole screen.
LED display
Apply the rated DC voltage and check that the "IN SERVICE" LED is lit in green.
Press the RESET key for 1 second and check that seven LEDs under the "IN SERVICE"
LED and two LEDs for monitoring jacks A and B are lit in red.
VIEW and RESET keys
Press the VIEW key when the LCD is off and check that the "Metering" screen is displayed
on the LCD.
Press the RESET key and check that the LCD turns off.
Keypad
Press any key on the keypad when the LCD is off and check that the LCD displays the
"MENU" screen. Press the END key to turn off the LCD.
Repeat this for all keys.
applied.
110
6 F 2 S 0 7 8 9