Replacing Failed Modules - Toshiba GRT100 Series Instruction Manual

Transformer protection relay
Hide thumbs Also See for GRT100 Series:
Table of Contents

Advertisement

If no message is shown on the LCD, this means that the failure location is either in the DC power
supply circuit or in the microprocessors mounted on the SPM module. Then check the
"ALARM" LED. If it is off, the failure is in the DC power supply circuit. If it is lit, open the relay
front panel and check the LEDs mounted on the SPM module. If the LED is off, the failure is in
the DC power supply circuit. If the LED is lit, the failure is in the microprocessors.
In the former case, check if the correct DC voltage is applied to the relay.
If so, replace the IO1 module mounting the DC/DC converter and confirm that the "ALARM"
LED is turned off.
In the latter case, replace the SPM module containing the processors and confirm that the
"ALARM" LED is turned off.
When a failure is detected during regular testing, it will not be difficult to identify the failed
module to be replaced.
Note:
When a failure or an abnormality is detected during the regular test, confirm the following
first:
- Test circuit connections are correct.
- Modules are securely inserted in position.
- Correct DC power voltage with correct polarity is applied and connected to the correct
terminals.
- Correct AC inputs are applied and connected to the correct terminals.
- Test procedures comply with those stated in the manual.
6.7.3

Replacing Failed Modules

If the failure is identified to be in the relay module and the user has spare modules, the user can
recover the protection by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level
is not recommended.
Check that the replacement module has an identical module name (VCT, SPM, IO1, IO2, etc.)
and hardware type-form as the removed module. Furthermore, the SPM module should have the
same software name.
The module name is indicated on the bottom front of the relay case. The hardware type-form is
indicated on the module in the following format:
Module name
Hardware type-form
VCT
G1PC2-
SPM
G1SP-
IO1
G1IO1-
IO2
G1IO2-
IO3
G1IO3-
HMI
--
 137 
6 F 2 S 0 7 8 9