Toshiba GRT100 Series Instruction Manual page 116

Transformer protection relay
Hide thumbs Also See for GRT100 Series:
Table of Contents

Advertisement


Single-phase
current
source


DC
power

supply

DC
voltmeter

Figure 6.5.1 Operating Current Value Test Circuit (Model 100s, 200s)
The output signal numbers of the DIF elements are as follows:
 Press 4 (= Logic circuit) on the "Test" sub-menu screen to display the "Logic circuit"
screen.
 Enter a signal number 44 to observe the DIF-A operation at monitoring jack A and press
the ENTER key.
 Apply a test current to A-phase current terminals and change the magnitude of the current
applied and measure the value at which the element DIF-A operates.
Check that the measured value is within 7% of the theoretical operating value.
Theoretical operating value = (CT secondary rated current)  (ik setting)
Percentage restraining characteristics
The percentage restraining characteristic is tested on the outflow current (I
(I
) plane as shown in Figure 6.5.2. The characteristic shown in Figure 6.5.2 is equivalent to the
in
one on the differential current (Id) and restraining current (Ir) plane shown in Figure 2.11.1.
A
Element
Signal number
DIF-A
44
DIF-B
45
DIF-C
46
 115 
6 F 2 S 0 7 8 9
GRT100
TB 1 -1
I a
- 2
Monitoring
jack
TB 4 - A16
- A17
E
) and infeed current