4.2.4.2
Displaying the Status of Binary Inputs and Outputs
To display the binary input and output status, do the following:
 Select 2 (= Status) on the top "MENU" screen to display the "Status" screen.
 Select 2 (= Binary I/O) to display the binary input and output status.
The display format is shown below.
[
Input (IO1)
BI1
BI2
Input (IO2)
BI14
BI15
Output (IO1-trip) TP-1
TP-2
Output (IO2)
BO1
BO2
Output (IO3)
BO1
BO2
Lines 1 and 2 show the binary input status. BI1 to BI16 corresponds to each binary input signal.
For details of the binary input signals, see Appendix G. The status is expressed with logical level
"1" or "0" at the photo-coupler output circuit. IO1 and IO2 in the table indicate the name of the
module containing the binary input circuits.
Lines 3 to 5 show the binary output status. TP-1 to TP-5 of line 3 corresponding to the tripping
command output. FAIL of line 4 corresponds to the relay failure output. Other outputs expressed
with BO1 to BO13 are configurable. The status of these outputs is expressed with logical level
"1" or "0" at the input circuit of the output relay driver. That is, the output relay is energized when
the status is "1".
IO1 to IO3 in the table indicate the names of the module containing the binary output relays.
To display all the lines, press the
/ 2
B i n a r y
i n p u t
I n p u t
( I O 1 )
I n p u t
( I O 2 )
O u t p u t ( I O 1 - t r i p )
O u t p u t ( I O 2 )
O u t p u t ( I O 3 )
BI3
BI4
BI5
BI6
BI16
TP-3
TP-4
TP-5
BO3
BO4
BO5
BO6 BO7 BO8 BO9 BO10 BO11 BO12 FAIL
BO3
BO4
BO5
BO6 BO7 BO8 BO9 BO10 —
&
o u t p u t
[ 0 0 0
0 0 0
[ 0 0 0
[ 0 0 0
0 0
[ 0 0 0
0 0 0
[ 0 0 0
0 0 0
BI7
BI8
BI9
BI10
and
keys.
 79 
6 F 2 S 0 7 8 9
3 /
5
0 0 0
0 0 0
0
]
]
]
0 0 0
0 0 0
0 0
]
0 0 0
0
]
BI11
BI12
BI13
BO13 —
]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents